IRIS is an addressable fire alarm panel with 1 to 4 loops and maximum coverage of 96 zones. Up to 250 devices can be connected to every system loop. The information for the system status is visualized on sensitive graphic display and LED indication for zones and troubles. With special 2 steps of alarm level working algorithm the false alarms are effectively minimized. The panel has a comprehensive day/night mode facility. The panel supports two communication protocols: Teletek Electronics (IRIS TTE loop) and System Sensor series (IRIS SS loop) according to the type of devices used. In the configuration of the IRIS panel both TTE and SS Loops can be implemented at the same time. Up to 64 IRIS panels can be connected in Ethernet network or RS485 redundant network. Direct programming with ProsTE software is available.

tanım

  • Loops: 1 to 4 (both TTE and SS loops can be mounted in random configuration)
  • Devices per loop: 250 (TTE loop)/ 198 (SS loop)
  • Standard: EN54 – 2/4 certified
  • Programmable inputs/outputs: up to 250
  • Zones: 96
  • Outputs (monitored, relay): 4
  • Outputs (non-monitored, programmable, relay): 4, 15A@24VDC
  • Memory LOG: 10 000 events
  • Panels in Ethernet network (built in TCP/IP): Up to 64
  • Panels in RS485 redundant network (optional module): Up to 64
  • Thermal printer: Optional
  • Display: 320/240 touch screen
  • Multi language support: Yes (English, Italian, Portuguese, Russian, Turkish, Polish, Croatian, Dutch, Latvian, French, Bulgarian currently available)
  • Programming: ProsTE software
  • Auto addressing function
Main Power Supply ~230 VAC +10%/-15%
Frequency 50/ 60Hz
Back-up Power Supply 1 battery, 12V/ 18Ah
Electrical output 7A
Operating temperature -5°C to +40°C
Weight (without battery) 6kg
Dimensions of metal bottom 441x331x80mm
Dimensions of front cover 461x344x45mm

Ürün Dökümanları

Yazılım

Observer 32_ver.2.4.1

 

Observer 64_ver.2.4.1

 

Guard View ver.2.1

Kılavuzlar

IRIS battery calculator English

 

IRIS SS loop calculator English

Sertifikalar

IRIS and IRIS Repeater – 2831 CPR Certificate LPCB

 

IRIS – EN54-13 Certificate KIWA

 

IRIS, SIMPO, MAG8 – TSE Certificate

Technical Documentation

IRIS – Installation and programming manual (English)
Önceki Yazı
Sonraki Yazı

BİZE ULAŞIN

HARİTADAKİ YERİMİZ